Single-phase
D9-M Series
D11-M Series
D11-M 20(10)Kv Off-load Distribution Transformers

  Brief  introduction

  • 20Kv D11 single-phase transformers are off-load outdoor oil type transformers designed for areas with low annual power load.

  • The product shortens power distribution radius thus reducing line loss during the transmission. The phase load unbalance can be readily controlled, voltage compliance rate improved, which effectively improve the power supply quality.

  • The product is ideal for residential area, railway and street lightening, rural power grid, remote areas, scattered villages etc.

    

  Features

  • Pole-mounted installation, small size, high overload capacity, easy maintenance.
  • Cold-rolled grain-oriented high-silicone-content steel, step-up lamination, low no-load loss, and low no-load current.
  • First Grade oxygen-free copper, new windings structure.
  • Hermetically sealed oil tank.
  • Vacuum oil-filling technology.
  • Low noise emission.

SELECTION CHART

  20KV PRIMARY ,400V SECINDARY

型号
Type
容量
Capacity
(kVA)
电压组合(HV/LV) 联结组
标号
Connection
空载损耗
No-Load
loss(w)
负载损耗
Load
loss(w)
空载电流
No-Load
Current(%)
短路阻抗
Impedance
Voltage(%)
轨距
Gauge
(mm)
高压
HV(kV)
分接范围
(%)
低压
LV(kV)
D11-M-5/10 5

20

±5%

 

0.22~0.24

Ii0

34 210 4.0 3.5 200*300
D11-M-10/10 10 50 250 3.5 200*300
D11-M-16/10 16 58 325 3.2 200*300
D11-M-20/10 20 70 385 3.0 200*300
D11-M-30/10 30 85 515 2.8 300*300
D11-M-40/10 40 120 680 2.5 300*300
D11-M-50/10 50 135 790 2.3 300*300
D11-M-63/10 63 160 830 2.1 300*400
D11-M-80/10 80 180 975 2.0 300*400
D11-M-100/10 100 210 1165 1.8 400*400
D11-M-125/10 125 235 1365 1.9 400*400
D11-M-160/10 160 270 1575 1.7 400*400