Introduction
- European style pad mounted transformers are distinguished by their very low overground height and minimal built-up area. They are exceptionally easy to transport and simple to install. The maintenance is also quite simple, no special duty needed to attend the station. They can be installed right in the load centre, thus improving the supply quality, reducing energy loss and enhancing the reliability of power supply.
- Sub-station series(European Style box)
|
Features
- The substation consists of high voltage switchgears, low voltage power distribution panel, power distribution transformers and the housing. Air type load switch is used for high-voltage line, transformer is either dry or oil type. The housing is also designed and built with good ventilation structure, improved insulation, along with upper and lower ventilation air duct, the temperature rises caused by outdoor solar radiation on transformer chamber and both high and low voltage chamber can be reduced to minimum. Upon request, the housing can be equipped with forced ventilation devices and automatic temperature control device. Each independent unit is installed with complete control, protection, data display and lighting systems.
低压主回路方案号(The Number Of LV Main Circuit Design)
主回路线路图 |
|
|
|
|
分类 |
1、无补偿单极系统 |
2、有补偿单极系统 |
3、有补偿多级系统 |
4、刀熔开关简化系统 |
方案号及说明 |
102二回路出线 |
202二回路出线 |
301一加二回路出线 |
402二回路出线 |
103三回路出线 |
203三回路出线 |
302二加二回路出线 |
403三回路出线 |
104四回路出线 |
204四回路出线 |
303二加三回路出线 |
404四回路出线 |
105五回路出线 |
205五回路出线 |
304二加四回路出线 |
405五回路出线 |
106六回路出线 |
206六回路出线 |
305三加三回路出线 |
406六回路出线 |
107七回路出线 |
207七回路出线 |
306三加四回路出线 |
407七回路出线 |
108八回路出线 |
208八回路出线 |
307四加四回路出线 |
408八回路出线 |
|
|
308五加五回路出线 |
409九回路出线 |
|
|
309六加六回路出线 |
|
|
单位UNIT |
项目ITEN |
参数DATA |
高压单元 |
额定频率 Rated Frequency |
Hz |
50 |
额定电压 Rated Vol. |
kV |
6 10 35 |
最高工作电压 Max working Vol. |
kV |
6.9 11.5 40.5 |
工频耐受电压Power Frequency Withstand Vol. |
|
|
对地和相间/隔离断口 |
kV |
32/36 42/48 95/118 |
雷电冲击耐压Ughining Imputse Withstand Vol. |
|
|
对地和相间/隔离断口 |
kV |
60/70 75/85 195/215 |
额定电流Rated Current |
A |
400 630 |
额定短时耐受电流 Rated Short Withstanding Current |
kA |
12.5(2S) 16(2S) 20(2S) |
额定峰值耐受电流 Rated Peak Withstand Current |
kA |
31.5 40 50 |
低压单元 |
额定电压 Rated Vol. |
V |
380 220 |
主回路锁定电流 Main Circuit Rated Current |
A |
100~3200 |
额定短时耐受电流 Rated Short Withstanding Current |
kA |
15 30 50 |
额定峰值耐受电流 Rated Peak Withstand Current |
kA |
30 63 110 |
支路电流 Branch Current |
A |
10~800 |
分支回路数 Circuit Num in Branch |
路 |
1~12 |
补偿容量 Compensution Capacity |
kVar |
0~360 |
变压器单元 |
额定电压 Rated Capacity |
KVA |
50~2000 |
短路阻抗 Impedonce Vol. |
% |
4~6 |
分接范围 Topping Range |
|
2*2.5% 5% |
联结组别 Connection Symbol |
|
Yyn0 Dyn11 |
高压主回路方案号(The Number Of HV Main Circuit Design)
主回路线路图 |
|
|
|
|
|
分类 |
1、单端不带计量 |
2、单端带计量 |
3、环网不带计量 |
4、环网带计量 |
5、双端 |
方案号及说明 |
11、无带电显示 |
21、无带电显示 |
31、进线端不带接地开关 |
41、进线端不带接地开关 |
51、无带电显示、不带计量 |
|
|
|
|
|
12、有带电显示 |
22、有带电显示 |
32、变压器倒不带接地开关 |
42、计量置于主开关前 |
52、有带电显示、不带计量 |
|
|
|
|
|
|
23、计量置于主开关前 |
33、带三个接地开关 |
43、带三个接地开关 |
53、带计量 |
|
|
|
|
|
|
|
|
|
54、变压器端不带接地开关 |
|